Model NO.
YCS1
Voltage Regulating Mode
Frequency Modulation Type
Power Supplying System
Level 1 Power Distribution Equipment
Energy Transmission
Two-way Transmission
Certification
CE
Transport Package
Standard Export Package
Trademark
CNC
Origin
China
HS Code
85365000
Production Capacity
1, 000 PCS/Day
Product Description
1 - 50W 380V Electrical Switch ats hot step down power supply
1.YCS1 automatic transfer switch (ATSE) is set the switches and control logic integrated without additional controller, achieve integration of automatic electro mechanical switch, voltage detection, frequency detection, communication interface, electrical, mechanical interlocking functions, automatic, electric remote emergency manual control.2.This is the logical control panel from various logical order to manage the machines, operate with the gearbox to achieve, switching spring motor storage, instantaneous release of the acceleration, rapid access to sub-circuit or circuits conversion, it is obvious by the state security confinement, greatly improved the performance of various electrical and mechanical properties.
3.YCS1 switches overall design for the metal shell, compact solid. YCS1 switches, control of some of the mental shell , the shell switching components used fiberglass unsaturated polyester resin manufacturing, with a strong dielectric properties, protection and reliability of the operational safety.
Switch power supply system applicable to changeover the main power supply and backup power supply automatically or two sets load equipment and safety isolation automatically.
Switch appearance is beautiful, creative, simple, and small size. The entire function is an ideal choice in different occasions.
Performance and Characters
1.Adopt the double row type composite contact, side pull institutions, micro motor prestore and microelectronics control technology, come true zero flashover (no arcing chamber).
2.Reliable electrical and mechanical interlocking chain, the implement of the components independently with islation switch, the use of safe and reliable.
3.Using over zero technology, the state of emergency can be enforced under the zero(cut down the 2 ways in the meanwhile) to meet the needs of Fire Fighting.
4.Executive load isolation switch using a single motor-driven, transfer reliable smooth, no noise, little impact.
5.Operators drive only in the implementation of the electrical load isolation by switching transient current, steady work without providing current, energy-saving significantly.
6.Executive load disconnector chain with a mechanical device used to ensure that reliable standby power of non-interference in each other.
7.Obvious off position indicator, padlocks and other functions, high reliability and service life of more than 8000 times.
8.Mechatronics design, switching conversion accurate, flexible, smooth and adopt international advanced logic control technology, anti-interference capability, without external interference.
9.Cooperation with the main power on and standby power off, or the main power off and standby on, the main power and standby power are both off, three kinds stability working.(I-O-II)
10.Easy installation, the control circuit return way adopt the connect and insert terminal connector.
11.Four operator models: emergency manual operation, electric remote control operation, emergency disconnected operation under the automatic stating, automatic control operations.
Life(N-R-N circle) and Specifications of Automatic Transfer Switch
20A~1600A Installation Dimensions
1.Adopt the double row type composite contact, side pull institutions, micro motor prestore and microelectronics control technology, come true zero flashover (no arcing chamber).
2.Reliable electrical and mechanical interlocking chain, the implement of the components independently with islation switch, the use of safe and reliable.
3.Using over zero technology, the state of emergency can be enforced under the zero(cut down the 2 ways in the meanwhile) to meet the needs of Fire Fighting.
4.Executive load isolation switch using a single motor-driven, transfer reliable smooth, no noise, little impact.
5.Operators drive only in the implementation of the electrical load isolation by switching transient current, steady work without providing current, energy-saving significantly.
6.Executive load disconnector chain with a mechanical device used to ensure that reliable standby power of non-interference in each other.
7.Obvious off position indicator, padlocks and other functions, high reliability and service life of more than 8000 times.
8.Mechatronics design, switching conversion accurate, flexible, smooth and adopt international advanced logic control technology, anti-interference capability, without external interference.
9.Cooperation with the main power on and standby power off, or the main power off and standby on, the main power and standby power are both off, three kinds stability working.(I-O-II)
10.Easy installation, the control circuit return way adopt the connect and insert terminal connector.
11.Four operator models: emergency manual operation, electric remote control operation, emergency disconnected operation under the automatic stating, automatic control operations.
Life(N-R-N circle) and Specifications of Automatic Transfer Switch
Rated current (Ith) | 20 A | 40 A | 60 A | 80 A | 100 A | 125 A | 160 A | 250 A | 400 A | 630 A | 800 A | 1000 A | 1250 A | 1600 A | |
Rated insulation voltage (Ui) | 750V | 1000V | |||||||||||||
Rated concussion withstand voltage (Uimp) | 8kV | 12kV | |||||||||||||
Rated working voltage (Ue) | AC440V | ||||||||||||||
Rated working current(Ie) | AC-31A | 20 | 40 | 63 | 80 | 100 | 125 | 160 | 250 | 400 | 630 | 800 | 1000 | 1250 | 1600 |
AC-35A | 20 | 40 | 63 | 80 | 100 | 125 | 160 | 250 | 400 | 630 | 800 | 1000 | 1000 | 1600 | |
AC-33A | 20 | 40 | 63 | 80 | 100 | 125 | 160 | 250 | 400 | 400 | 630 | 800 | 800 | 1000 | |
Rated connection capacity | 10Ie | ||||||||||||||
Rated breaking capacity | 8Ie | ||||||||||||||
Rated limited short circuit current (Is) | 50kA | 70kA | 100kA | 120kA | |||||||||||
Rated short-time withstand current (Is) | 7kA | 9kA | 13kA | 26kA | 50kA | ||||||||||
Transfer I-II or II-I | 0.45s | 0.6s | 1.2s | ||||||||||||
Control power voltage | DC24V, 48V, 110V AC220V | ||||||||||||||
Electrical consumption | |||||||||||||||
Rated Start | 300W | 325W | 355W | 400W | 440W | ||||||||||
frequency Normal | 55W | 62W | 74W | 90W | 98W | ||||||||||
Weight(kg) 4 pole | 7.0 | 7.2 | 7.2 | 7.2 | 7.5 | 7.5 | 8.8 | 9.0 | 16.5 | 17 | 32 | 36 | 40 | 43 |
20A~1600A Installation Dimensions
Specification | Total size | Switch installation | Connection terminal | ||||||||||||||||||||
A | A1 | B | B1 | C | E | G | H | J | K | L | N | O | P | R | S | T | U | V | ΦX | Y | Y1 | Z | |
20A | 279 | 243 | 106 | 103 | 169 | 145 | 115 | 19 | 229 | 85 | 7 | 76 | 153 | 30 | 14 | 18 | 2.5 | 103 | 20 | 6 | 41 | 94 | 3 |
40A | 279 | 243 | 106 | 103 | 169 | 145 | 115 | 19 | 229 | 85 | 7 | 76 | 153 | 30 | 14 | 18 | 2.5 | 103 | 20 | 6 | 41 | 94 | 3 |
63A | 279 | 243 | 106 | 103 | 169 | 145 | 115 | 19 | 229 | 85 | 7 | 76 | 153 | 30 | 14 | 18 | 2.5 | 103 | 12 | 6 | 41 | 94 | 3 |
80A | 279 | 243 | 106 | 103 | 169 | 145 | 115 | 19 | 229 | 85 | 7 | 76 | 153 | 30 | 14 | 18 | 2.5 | 103 | 12 | 6 | 41 | 94 | 3 |
100A | 279 | 243 | 106 | 103 | 169 | 145 | 115 | 19 | 229 | 85 | 7 | 76 | 153 | 30 | 14 | 18 | 2.5 | 103 | 12 | 6 | 41 | 94 | 3 |
125A | 322 | 300 | 135 | 128 | 230 | 189 | 115 | 10 | 284 | 102 | 7 | 91 | 190 | 36 | 20 | 25 | 3.5 | 127 | 18 | 9 | 55 | 125 | 4 |
160A | 322 | 300 | 135 | 128 | 230 | 189 | 115 | 10 | 284 | 102 | 7 | 91 | 190 | 36 | 20 | 25 | 3.5 | 127 | 18 | 9 | 55 | 125 | 4 |
250A | 406 | 362 | 163 | 142 | 230 | 189 | 143 | 4 | 343 | 80/102 | 7 | 91 | 252 | 36 | 25 | 30 | 3.5 | 142 | 15 | 11 | 57 | 125 | 11 |
400A | 552 | 433 | 234 | 222 | 230 | 273 | 189 | 14 | 416 | 180 | 9 | 93 | 323 | 50 | 40 | 38 | 5 | 222 | 18 | 13 | 83 | 193 | 19 |
630A | 552 | 433 | 250 | 222 | 284 | 273 | 189 | 14 | 416 | 99/180 | 9 | 93 | 323 | 65 | 40 | 45 | 6 | 222 | 18 | 13 | 83 | 193 | 19 |
800A | 760 | 633 | 328 | 250 | 284 | 350 | 443 | 28 | 613 | 220 | 11 | 87 | 526 | 65 | 60 | 64 | 8 | 250 | 31 | 13 | 109 | 254 | 54 |
1000A | 760 | 633 | 328 | 250 | 363 | 350 | 443 | 28 | 613 | 220 | 11 | 87 | 526 | 120 | 60 | 64 | 8 | 250 | 31 | 13 | 109 | 254 | 54 |
1250A | 760 | 633 | 336 | 250 | 363 | 350 | 443 | 28 | 613 | 220 | 11 | 87 | 526 | 120 | 80 | 68 | 8 | 250 | 21 | 13 | 110 | 254 | 54 |
1600A | 760 | 633 | 336 | 250 | 363 | 350 | 443 | 28 | 613 | 220 | 11 | 87 | 526 | 120 | 80 | 68 | 10 | 250 | 21 | 13 | 110 | 255 | 54 |