Basic Info.
Model NO.
DR-120-24
Voltage Regulating Mode
Frequency Modulation Type
Power Supplying System
Terminal Power Distribution Equipment
Energy Transmission
One-way Transmission
Modulation System
PWM
Certification
CE, RoHS, ISO
Brand
Leyu
Power
120W
Output
24V
Color
Sliver
Input
85-264VAC
MOQ
1PCS
OEM
Acceptable
Efficiency
88%
Weight
1.2kg
Transport Package
Carton Packing
Specification
65.5*125.2*100mm(W*H*D)
Trademark
LEYU
Origin
China
HS Code
8504401990
Production Capacity
60000PCS/Month
Product Description
DR-120-24 120W 12V 24V 36V 48V DC Single Output DIN Rail Power Supply
Features:
Universal AC input/ full range
Protections: Short circuit/ Over load/ Over voltage
Cooling by free air convection
Can be installed on DIN rail TS-35/7.5 or 15
Isolation class 2
LED indicator for power on
100% full load burn-in test
2 years warranty
Universal AC input/ full range
Protections: Short circuit/ Over load/ Over voltage
Cooling by free air convection
Can be installed on DIN rail TS-35/7.5 or 15
Isolation class 2
LED indicator for power on
100% full load burn-in test
2 years warranty
SPECIFICATIONS | |||
OUTPUT | |||
Model | DR-120-12 | DR-120-24 | DR-120-48 |
DC Voltage | 12V | 24V | 48V |
Rated Current | 10A | 5A | 2.5A |
Current Range | 0-10A | 0-5A | 0-2.5A |
Rated Power | 120W | 120W | 120W |
Ripple & Noise | 80mVp-p | 80mVp-p | 100mVp-p |
Voltage Adj. Range | 12-14V | 24-28V | 48-53V |
Voltage Tolerance | ±2% | ±1% | ±1% |
Line regulation | ±0.5% | ±0.5% | ±0.5% |
Load regulation | ±1% | ±1% | ±1% |
Setup, Rise Time | 500ms,70ms/230VAC 500ms,70ms/115VAC at full load | ||
Hold Up Time | 36ms/230VAC 32ms/115VAC at full load | ||
Voltage Range | 88~132VAC/176~264VAC selected by switch 47~63Hz; 248~370VDC | ||
AC Current | 2.6A/115VAC 1.6A/230VAC | ||
Efficiency | 80% | 84% | 85% |
Inrush Current | Cold start 20A/115V 40A/230V | ||
Leakage Current | <3.5mA/240VAC | ||
Over Load | 105%~150% rated output power | ||
Protection type: Constant current limiting, recovers automatically after fault condition is removed | |||
Over Voltage | 15-16.5V | 29-33V | 58-65V |
Protection type: Shut down o/p voltage, re-power on to recover | |||
Over Temp. | 85ºC±5ºC(TSW1) | 90ºC±5ºC(TSW1) | 90ºC±5ºC(TSW1) |
Protection type: Shut down o/p voltage, recovers automatically after temperature goes down | |||
Working Temp., Humidity | -10ºC~+60ºC; 20%~90% RH non-condensing | ||
Storage Temp., Humidity | -20ºC~+85ºC; 10%~95%RH | ||
Vibration | 10~500Hz, 2G 10min./1cycle, period for 60min, each along X, Y, Z axes | ||
Withstand Voltage | I/P-O/P: 3KVAC I/P-FG: 1.5KVAC O/P-FG: 0.5KVAC | ||
Isolation Resistance | I/P-O/P, I/P-FG, O/P-FG: 100M Ohms / 500VDC/25ºC/70%RH | ||
Safety Standard | Design refer to UL508,UL60950-1,TUV EN60950-1 | ||
EMC Standard | Design refer to EN55011,EN55022,EN61000-3-2,-3,EN61000-4-2,3,4,5,6,8,11,EN55024,EN61000-6-2(EN50082-2), heavy industry level, criteria A | ||
Dimension | 65.5*125.2*100mm(L*W*H) | ||
Weight | 0.79Kg | ||
Packing | 20pcs/carton/16.5kg/1.29CUFT | ||
NOTE | |||
1.All parameters NOT specially mentioned are measured at 230VAC input, rated load and 25ºC of ambient temperature. | |||
2. Ripple & noise are measured at 20MHz of bandwidth by using a 12" twisted pair-wire terminated with a 0.1μf & 47μf parallel capacitor. | |||
3.Tolerance: includes set up tolerance, line regulation and load regulation. | |||
4.The power supply is considered a component which will be installed into a final equipment. The final equipment must be re-confirmed that it still meets EMC directives. |