Basic Info.
Model NO.
NDR-120-12V
Voltage Regulating Mode
Frequency Modulation Type
Power Supplying System
Level 1 Power Distribution Equipment
Energy Transmission
One-way Transmission
Modulation System
PWM
Certification
CE, RoHS, CCC, CB
Brand
Funelec
Transport Package
Carton
Specification
CE and IEC
Trademark
FUNELEC
Origin
Wenzhou, China
HS Code
8535400000
Production Capacity
50000
Product Description
Switching power supply rail installation caliper power supply 120W slim power supply 12V 10A NDR-120-12V
Model | NDR-120-12 | NDR-120-24 | |
Output | DC output Voltage | 12V | 24V |
Voltage tolerance | ±1.0% | ±1.0% | |
Rated Current | 10A | 5A | |
Related Power | 120w | 120w | |
Wave&Noise | 80mVp-p | 150mVp-p | |
Adjustable range for DC Voltage | ±10% | ±10% | |
Set up,rise,hold up time | 800ms 600ms 50ms | ||
Input | Voltage Range | 85 ~ 264VAC 47-63HZ 120-370VDC | |
Input Current | 1A/115VAC 0.5A/230VAC | ||
Efficiency | 77% | 82% | |
AC inrush current | Cold start current 15A/115V 30A /230VAC | ||
Leakage current | <0.5mA/240VAC | ||
Protection | Overload | Related output power 105-135% start overload protection | |
Protection type: cutoff output, recovery after restart power | |||
Over voltage | 13.8V-16.2V | 27.6V-32.4V | |
Hiccup mode,recovers automatically after fault condition | |||
Environment | Working temp humidity | -10~+60°C 20%~90%RH | |
Stor temp, humidity | -20~+85°C 20%~90%RH Non-condensing | ||
Safety | Withstand voltage | I/P-O/P:1.5KVAC 1min | |
I/P-FG:1.5KVAC 1min | |||
O/P-FG:0.5KVAC 1min | |||
Standard | Safety standard | Fit UL1012 | |
Refer | Design refer to GB4943,UL60950,EN60950 | ||
EMC standard | Design refer to GB9254,EN55022 Class A | ||
Size | size | 40*W125.5*H113.5mm | |
Package | 0.52kg, |